Installation of Filters

For optimum EMI performance, the correct mounting of any filter is essential. It is important to ensure low as possible earth bond impedance to the unpainted base or mounting flange of the filter. This is to obtain the best possible insertion loss from the filter, and to carry away high pulse currents in transient suppressed filters. 

 


It is recommended that the filters are mounted on a steel surface which has been electroplated with tin or zinc where possible. This should be unpainted and must be flat or smooth. Whilst other materials and finishes may be acceptable, the user should give consideration to the shielding and earth bonding properties, and possible galvanic corrosion effects of any material used. In most cases, "conductive" paint finishes are unacceptable as they do not permit a sufficiently good earth bond to be made. 

Penetration tubes are used to pass cables through the base of the filter and the mounting surface. These must provide a complete RF seal. Dedicated fixings kits can be supplied upon request.

Filter sizes and cable entries are designed to be a minimum for the filter current rating. The user is advised to verify that the standard filter terminal compartment and cable entry sizes are suitable for this application, especially where oversize cables may be used to minimise cable volt drop.

Correct fitment of terminal compartment lids and gaskets should be observed, ensuring all lid screws are fitted and tightened to the specific torque.

Where several power filters are installed in close proximity, it is recommended they are vertically installed with at least 25mm spacing to assist with convection cooling. 

All conductors should pass through single cable entries in accordance with the IEE regulations to avoid eddy current heating effects.

A complete installation service can be arranged upon request.