MIL-STD 188-125-1 Acceptance Test by Jaxon Engineering for 32 Amp, 2 Line, Power Line Filter

 


EEP Filters have undergone extensive testing to ensure our filters meet the required standards expected by our customers. The testing criteria includes acceptance testing towards the MIL-STD-188-125-1 standard for pulse-current injection of:

  • E1 Short Pulse Testing
  • E2 Intermediate Pulse Testing

     

The filtering unit which has been tested comprises of two individual lines rated at 32A, 230V AC RMS at 50Hz which utilises high frequency capacitor technology and low loss magnetics.

Manufactured at EEP Filters manufacturing facility in Liverpool, the filter also comprises of two individual EPCOS B60 K275 surge protection varistor modules that monitor both lines for transient voltages.

The filtering unit was classified as a PPD (Point of Entry Protective Device), tested up to the MIL-STD-188-125-1 unrestricted Intrasite power line levels, with an observed result of “No damage or upset” and “Accepted residuals measured for unrestricted Intrasite levels”. The EEPF-32-2-PL filter was also tested for short circuit with an observed result of “Higher residuals measured for short circuit testing”.

From the testing provided by Jaxon Engineering in Colorado, this showed our filtering unit tested met all applicable PCI acceptance test requirements, which shows the filter designed and made by EEP Filters meet the requirements of MIL-STD-188-125-1.

For further information, please view the associated download.